HT1050
Fire extinguishers and cylinders testing unit up to 500 bar
Characteristics
The HT1050 is a manual unit for hydraulic testing of cylinders and fire extinguishers. The working cycle of the machine includes the following steps: filling the cylinder with water by electric pump, pressurizing the cylinder by pneumatic pump, and emptying the cylinder by electric pump. The stop of the pneumatic pump when the pressure is reached can be manual or automatic (optional). Testing time and no-leakage check are done manually.
In its basic configuration it can test one cylinder, but with the HT ramp it can perform pressurization on 10 cylinders max. (Filling and emptying steps are always done individually).
Dati tecnici
Modello | HT1050 |
Catalog code | MACP018 |
Voltage Frequency (VAC/HZ) | 400/50 three phase |
Cylinder places | 1 (up to 10 with optional HT ramp) |
Max testing pressure | 500 bar (to be specified in order) |
Productivity (10 min testing) | 100 min for 10 50L cylinders |
Productivity with HT ramp (10 min testing) | 75 min for 10 50L cylinders |
Compressed air supply | 6 bar - 700 L/min |
Overall dimensions (Lxlxh) | 700x600x1250 mm |
Tank size | Ø740 mm x 1350 mm (h) |
Weight | 185 Kg |
Standard components
25E thread adapters |
Accessories
Ht ramp up to 10 cylinder places |
Adapters for threads other than 25E |
Tank with customized features |